Parameter 3
]specif
ies the channel
on
which
to
make the
firdt measurement.
Parameter 6
specifies
thellnput Storage
location
in which to
store
the
firsf
channel
measurement.
lf multiple
repetitions afe
specified,
measurements
from
sequentialc$annels
are stored
in
adjacent
input
locations beginning
with the location
specified in
Parameter 6.
For Example, if there
are 5
stored
in
Parameter
location
in
the
Input
Storage
to
find the reference
temperature
this case
location 1 where
the
panel
re is stored. Parameters
7
and
8 are
the and
offset which convert the
measu to
engineering units.
The TC
instructions
the
measurement
in
units of
21X
MICROLOGGER
OVERVIEW
oC
when a
multiplier
of
1 and an offset of
0 are
used.
The
first example
was
explained
one
keystroke
at a time.
Instead
of
listing each keystroke,
the
following format
shows
the display after
a
value
is
keyed
in; the
use
of the
A key
to advance
to
the
next
entry
is
not shown.
This format
is
similar to that
used in the
PC208 EDLOG
program.
lf
you
have
followed
through
sample
program
1
and edited
the
program
in OV4.2,
your
21X
now has a 5
second
execution
interval and
lnstruction 17 in Table 1 .
To continue with
this
example
you
can
simply
advance
(key
A)
through
the execution interval and
Instruction
17
and check
the entries against
the following
listing. The new
entry
starts
with
the
second
instruction in the table.
lnstruction
(Loc.:Entry)
"1
01:5
01:P17
O2:P14
03:P92
Parameter
(Par.#:Entry)
01:1
01:1
02:1
03:5
04:1
05:1
06:2
07:1
08:0
01:0
02:60
03:10
Description
Enter Program Table
1
5 second
execution interval
Measure
panel
temperature
Store temp.
in
location
1
Measure
thermocouple temp.
(differential).
1 repetition.
Range code
(SmV,
slow).
Input channel of
TC.
TC type: copper-constantan.
Reference
temp
is stored
in
location 1.
Store
TC temp
in location
2.
Multiplier
of
1
(degrees
C)
Offset
of 0.
lf Time
0 minutes
into
the
interval.
60
minute
interual.
Set
Output
Flag
(Flag
0).
The
21X
is
programmed
to
measure
the
thermocouple
temperature every 5 seconds.
The lf Time
lnstruction,
p2,
sets
the Output
Flag at the beginning
of
each
hour.
Next,
the
instructions
for time
and
averagQ are
added.
ov-l3