CS225 Temperature String
21
8. Maintenance and Calibration
The CS225 string requires no maintenance or calibration.
9. Troubleshooting
Symptom: -9999 or NAN for temperature
1. Verify the green wire is connected to the control port specified by the
SDI12 measurement instruction.
2. Verify the red power wire is connected to a 12V terminal; check the
voltage with a Digital Volt Meter. If a switched 12V terminal is used,
temporarily connect the red wire to a 12V terminal (non-switched) for test
purposes.
Symptom: Sensor won’t respond to command
1. Expected address not used or has been changed.
a. In this case you may wish to confirm all addresses in use with the
“aI!” command in a trial & error fashion. You will be able to
determine the individual addresses of each temperature sensor.
2. Expected sensor address has been to match another sensor address already
in use.
a. When readdressing temperature sensors you must avoid giving
multiple sensors the same address. If this does occur you will no
longer be able to communicate with these sensors. Use the
“aA{!” command, where “a” is the affected address. This will
reset the affected sensors to their factory configured address
value.