Model HFP01SC Self-Calibrating Soil Heat Flux Plate
;Perform in-situ calibratation.
;
2: If time is (P92)
1: 1 Minutes (Seconds --) into a
2: 180 Interval (same units as above)
3: 30 Then Do
3: Z=X (P31)
1: 2 X Loc [ shf_mV ]
2: 4 Z Loc [ mV_0 ]
;Begin heating for calibration.
;
4: Do (P86)
1: 49 Turn On Switched 12V
;Used to filter data during and after calibration.
;
5: Do (P86)
1: 118 Set Flag 18 High
6: End (P95)
;End site calibration three minutes after calibration started.
;
7: If time is (P92)
1: 4 Minutes (Seconds --) into a
2: 180 Interval (same units as above)
3: 30 Then Do
;Measure voltage across current shunt resistor during calibration.
;This measurement is used to compute power.
;
8: Volt (Diff) (P2)
1: 1 Reps
2: 25 5000 mV, 60 Hz Reject, Fast Range
3: 10 DIFF Channel
4: 7 Loc [ V_Rf ]
5: .001 Mult
6: 0 Offset
9: Z=X (P31)
1: 2 X Loc [ shf_mV ]
2: 5 Z Loc [ mV_180 ]
;Turn off the soil heat flux plate heater.
;
10: Do (P86)
1: 59 Turn Off Switched 12V
11: End (P95)
;Stop filtering data.
;
12: If time is (P92)
1: 39 Minutes (Seconds --) into a
2: 180 Interval (same units as above)
3: 30 Then Do