Model HFP01SC Self-Calibrating Soil Heat Flux Plate
14: Average (P71)
1: 1 Reps
2: 1 Loc [ shf ]
15: Do (P86)
1: 29 Set Intermed. Proc. Disable Flag Low (Flag 9)
16: Sample (P70)
1: 1 Reps
2: 3 Loc [ cal ]
;Add other processing here.
;Call calibration routine.
;
17: Do (P86)
1: 8 Call Subroutine 8
*Table 2 Program
02: 0 Execution Interval (seconds)
*Table 3 Subroutines
;Calibration routine.
;
1: Beginning of Subroutine (P85)
1: 8 Subroutine 8
;Perform in-situ calibratation.
;
2: If time is (P92)
1: 1 Minutes (Seconds --) into a
2: 180 Interval (same units as above)
3: 30 Then Do
3: Z=X (P31)
1: 2 X Loc [ shf_mV ]
2: 4 Z Loc [ mV_0 ]
;Begin heating for calibration.
;
4: Do (P86)
1: 48 Set Port 8 High
;Used to filter data during and after calibration.
;
5: Do (P86)
1: 18 Set Flag 8 High
6: End (P95)
;End site calibration three minutes after calibration started.
;
7: If time is (P92)
1: 4 Minutes (Seconds --) into a
2: 180 Interval (same units as above)
3: 30 Then Do
11