CR10 and VW Sensors, 2002/12/18 3
Instruction 131
with AVW1 Interface
Instruction P131
Instruction 131 returns two values, a reading in Hz, and a
second value that can be used by the monitoring program to test
the quality of the reading. The instruction has 14 parameters.
Reps: Enter a 1. Do not use this instruction to obtain a second
reading. Instead, call instruction 131 a second time, after an
appropriate delay.
Range Option: Enter a 2 (or 1).
SE Channel: Choose an input channel.
Ex Channel: Choose an excitation channel.
Starting Freq (Hz): Enter a starting frequency for the excitation
sweep. See Sensors and Sweeps on page 5.
Ending Freq (Hz): Enter an ending frequency for the excitation
sweep. See Sensors and Sweeps on page 5.
T (Sweep, Units=ms): Enter the duration of the sweep in milli-
seconds. See Sensors and Sweeps on page 5.
N (no. of Steps): Enter the number of steps in the sweep fre-
quency. See the Sensor Table and Sweep Table for a value.
Delay after Excit. (Units=ms): Enter a delay of 25 milliseconds.
Cycles to Measure: Enter the number of cycles. See the Sensor
Table and Sweep Table for a value.
Rep Delay (Units = 0.01 sec): Enter zero.
Loc: Enter a label up to 9 characters long. PC208W then assigns
an input location. Behind the scenes, PC208 actually assigns two
input locations, one for the reading and the other for the com-
parison reading. Both readings are in Hz. The sample program
uses the label “Freq_1,” so PC208W automatically generates a
second label, “Freq_2.”
Mult: Enter 1.
Offset: Enter zero.