CS475, CS476, and CS477 Radar Water Level Sensor
5. Configuration
5.1 Default Settings
In most circumstances, the default settings (see Table 5-1) should be used.
Refer to Appendix B for other setting options and SDI-12 commands.
TABLE 5-1. Default Settings
Setting Default Setting
SDI-12 Address 0 (You only need to change this if two sensors are
connected to the same port; valid addresses are 0
through 9, A through Z, and a through z.)
Units of Measure 1 = feet
Water Conditions 1 = smooth; (typical peak to trough of wave ≤4 inches)
Power Operation
Mode
1=on (Sensor is always on until a new power operation
mode command is received.)
5.2 Startup Procedure
The basic startup procedure for the radar sensor is as follows:
1. Mount, wire, and install the sensor (see Sections 3 and 4).
2. Do a Start False Echo Learn command followed by a Send Data
command. The Start False Echo Learn command is an essential function
during the setup of the sensor (see Section 5.2.1).
3. Enter the current water level using the Set Water Stage command followed
by a Send Data command (see Section 5.2.2).
4. Refer to Appendix B if you want to change defaults for the address, units
of measure, water conditions, and power operation mode.
5. Program the datalogger to measure the sensor (see Section 6).
5.2.1 Start False Echo Learn
The settings are changed using the 25616 Adjustment/Display
Module or the terminal emulator in LoggerNet or PC400.
During normal communication, the datalogger sends the address,
together with a command, to the sensor. The sensor then replies
with a “response”.
NOTE
The Start False Echo Learn command is an essential function during the
startup of the sensor. It is also used during testing if a problem is encountered.
The command allows the unit to learn about false echoes (noise) in the area.
With the False Echo Learn command, you enter the actual distance to the water
surface, as measured in meters or feet, depending on the Unit setting. The
10