Campbell CR500 Specifiche Pagina 34

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 48
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 33
cR500
6.12 Troubleshooting
No Response
From
Datalogger
Using
CRl OKD
c.
Make sure
the battery has been installed, and
the
power
"oN".
Use
a
voltmeter
to measure the voltage
on the
12 V
and G
terminals on
the datalogger; the voltage must be between 9
and 16 VDC.
Disconnect
any sensor or
peripheral
wires connected
to
the
and 12 V terminals.
D. Disconnect
any communications or storage
peripherals
datalogger;--.*
E.
Reset
the datalogger by
turning the
power
switch to
"OFF",
to
"ON".
F. lf still no response,
callCampbell Scientific.
24
Vedere la pagina 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 47 48

Commenti su questo manuale

Nessun commento